Delta DPH Series - 50 - 300/500/600 KVA

IT administrators are faced with the constraints of rising rack power density and constrained data center space in today's IT-intensive environment with heavy data traffic driven by cloud, 4G/5G, and media streaming applications. Customers' needs for high power density, high power performance, and absolute availability are satisfied by Delta's cutting-edge modular UPS solutions. With a 50kW per module power density that leads the industry, the new Delta Modulon DPH series UPS 50-300/500/600 kVA delivers the highest space usage and shortest footprint. To optimize total cost of ownership (TCO), Modulon's DPH Series UPS is the best modular power protection for MW data centers.

Model

Power Rating

Input

Output

Interface

Conformance

Efficiency

DPH-300K

DPH-300K 100, 150, 200, 250, 300 kVA/kW, Power Module Quantity: Up to 6 units

  • Nominal Voltage 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
  • Voltage Range 305~478 Vac (full load), 228~478 Vac (70% load)
  • Current Harmonic Distortion < 3% **
  • Power Factor > 0.99
  • Frequency Range 40~70 Hz


  • Voltage 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
  • Voltage Harmonic Distortion ≤ 0.5% (linear load)
  • Voltage Regulation ± 1% (static)
  • Frequency 50/60 Hz ± 0.05 Hz
  • Overload Capability ≤ 125%: 10 minutes, ≤ 150%: 1 minute, > 150%: 1 second


Display

  • 10” color touch screen


  • RS232 x 1, Parallel port x 4, USB type A x 2, USB type B x 1, MODBUS x 1, Smart slot x 1, REPO x 1, EPO x 1, Input dry contact x 4, Output dry contact x 6, External battery temperature detection x 4, External switch/breaker status dry contact x 4, BMS (RJ45) x 1, Ethernet x 1



Optional 

  • Relay I/O card, Battery cabinet temperature sensor cable



Safety CE


  • AC-AC Up to 96.5%
  • ECO Mode 99%


DPH-500K

DPH-500K 300, 350, 400, 450, 500 * kVA, Power Module Quantity: Up to 9 units



DPH-600K



DPH-600K 500, 550, 600 kVA/kW, Power Module Quantity: Up to 12 units