| - HPH-160K 160 kVA* / 150 kW
- HPH-200K 200 kVA / 200 kW
| - Nominal Voltage 220/380 Vac, 230/400 Vac , 240/415 Vac (3-phase, 4-wire + G)
- Voltage Range 305~478 Vac (full load), 228~478 Vac (70% load)
- Current Harmonic Distortion ≤ 3% **
- Frequency 40~70 Hz
| - Voltage 220/380 Vac, 230/400 Vac , 240/415 Vac (3-phase, 4-wire + G)
- Voltage Harmonic Distortion ≤ 0.5% (linear load)
- Frequency 50/60 Hz
- Frequency Regulation ± 0.05 Hz (battery mode)
- Overload Capability ≤ 125%: 10 minutes, ≤ 150%: 1 minute
| 10” color touch screen | - Standard: External battery temperature detection x 4, External switch/breaker status dry contact x 4, Output dry contact x 6, Input dry contact x 4, Parallel port x 2, USB Port (Type A x 2
Optional - Relay I/O card, Battery cabinet temperature sensor cable
| - Safety CE, RCM
- UPS Classification According to IEC 62040-3 VFI-SS-111
| - AC-AC Up to 96.5%
- ECO Mode 99%
| - Nominal Voltage ± 240 Vdc
- Charge Voltage ± 272 Vdc (adjustable from 204 V to 312 V)
- Battery Number Configuration 30~46 pcs (default: 40 pcs)
| Environment - Operating Altitude 1000 meters (without derating)
- Operating Temperature 0~40℃
Audible Noise Relative Humidity Others - Parallel Redundancy and Expansion Maximum 8 units
- Remote Emergency Power Off: Yes
- Battery Start: Yes
|