HPH Series UPS, Three Phase, 20/30/40/60/80/100/120 kW

Best-in-class power protection with maximum power and cost efficiency

There is a solution hidden behind every excellent design. True online double-conversion from Delta For small and medium data centers and mission-critical applications needing extremely dependable power protection and unparalleled energy economy, the Ultron HPH Series is the answer. For greater Total Cost of Ownership (TCO) savings, the Ultron HPH Series UPS design features low iTHD (3%), 96% AC-AC, and 99% ECO mode energy efficiency. The Ultron UPS provides industry-leading AC-AC efficiency without compromising any available power needs with fully rated power (kVa=kW) without de-rating. The Ultron HPH watch-dog design further enhances increased availability.

Simply put, Delta's HPH Series UPS is a best-in-class power protection system (three phase 20/30/40/60/80/100/120 kVA UPS) that combines the highest amount of available power, unparalleled energy economy, and excellent power performance with a key advantage: TCO savings. In addition to businesses involving industrial equipment, communication systems, computer network systems, medical systems, monitoring systems, and more, HPH is a great option for data centers. Since the Ultron HPH series UPS was introduced in 2013, it has been widely embraced by customers and professional organizations all over the world. For example, HPH 20kVA and 30kVA UPS are now being used by luxury car manufacturers in Germany, important telecommunications providers in Asia, and international medical equipment suppliers in India, to name a few.

Model UPS

UPS Integrated Battery - Batteries Inside

UPS Integrated Battery - No Batteries Inside

Power Rating

Input

Voltage Range

Other

Other

Other


  • HPH-20K
  • HPH-30K
  • HPH-40K
  • HPH-60K
  • HPH-80K
  • HPH-100K
  • HPH-120K




  • HPH-20K-B
  • HPH-30K-B
  • HPH-40K-B


  • HPH-20K-BN
  • HPH-30K-BN
  • HPH-40K-BN


  • HPH-20K 20 kVA / 20 kW
  • HPH-30K 30 kVA / 30 kW
  • HPH-40K 40 kVA / 40 kW
  • HPH-60K 60 kVA / 60 kW
  • HPH-80K 80 kVA / 80 kW
  • HPH-100K 100 kVA / 100 kW
  • HPH-120K 120 kVA / 120 kW


Nominal Voltage 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)


  • HPHH-20K/30K/40K 300~477 Vac (full load), 228~300 Vac (70~100% load)
  • HPHH-60K/80K/100K/120K 332~477 Vac (full load), 228~332 Vac (63~100% load)


Input

  • Nominal Voltage 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)

 

Voltage Range

  • HPHH-20K/30K/40K 300~477 Vac (full load), 228~300 Vac (70~100% load)
  • HPHH-60K/80K/100K/120K 332~477 Vac (full load), 228~332 Vac (63~100% load)


Frequency

  • 40~70 Hz


Power Factor

  • > 0.99 (full load)



Current Harmonic Distortion

  • < 3%

 

Output

  • Voltage 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)
  • Voltage Regulation ± 1%

 


 



Voltage Harmonic Distortion

  • HPH-20K/30K/40K < 1.5% (linear load)
  • HPH-60K/80K/100K/120K < 2% (linear load)


Overload Capability

  • ≤ 105%: continuous
  • 106~≤ 125%: 10 minutes
  • 126~≤ 150%: 1 minute
  • > 150%: 1 second

 

Output Power Factor

  • 1



Frequency

  • 50/60 Hz ± 0.05 Hz


Battery

  • Battery Voltage 240 Vdc
  • Type Support SMF/VRLA/Tubular/Ni-Cd

Quantity

  • HPHH-20K/30K/40K 32~50 pcs
  • HPH-60K/80K/100K/120K 32~46 pcs ***



 

Charge Current (Max.) Built-in

  • HPH-20K 5 A
  • HPHH-30K/40K 9 A
  • HPH-60K 10 A
  • HPHH-80K 15 A
  • HPH-100K/120K 20 A

 

Communication Interfaces

  • SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1 *

 

Conformance

  • Safety CE, RCM




UPS Classification 

  • IEC 62040-3
  • VFI-SS-111


Other Features 

  • Parallel Redundancy Up to 4 units
  • Emergency Power Off Yes (local and remote)
  • Maintenance Bypass Switch Yes