Delta UPS N 1/2/3 KVA

High-performance power protection with greater energy savings

A real on-line, double-conversion 1 kVA, 2 kVA, or 3 kVA UPS contained in a small tower is the Amplon N Series UPS. Double-conversion UPS systems can control output frequency between 50 and 60 hertz and are lighter than other types of UPSs. Such systems can take electricity from an AC line as pulse-free sine waves thanks to their power-factor adjustment capabilities. With an output power factor of 0.9 and up to 93% AC-AC efficiency for increased energy savings, it has several advantageous features.

Both UPS systems take less current from the battery and continuously maintain battery voltage. In case of a power outage, built-in batteries supply key loads with steady, uninterrupted power. Users benefit from higher power quality and nearly optimum electrical output performance. Workstation, POS, ATM, and household appliance disruptions are eliminated by the Amplon N Series. You can add an external battery pack to improve availability for crucial applications if your backup time needs are longer.

Model

Power Rating

Input

Output

Receptacle

Efficiency

Efficiency

  • N-1K
  • N-2K
  • N-3K


  • N-1K 1 kVA / 0.9 kW
  • N-2K 2 kVA / 1.8 kW
  • N-3K 3kVA / 2.7 kW


  • Nominal Voltage 220/230/240 Vac
  • Voltage Range 175~280 Vac (full load), 80~175 Vac (50-100% load)
  • Frequency 50/60 Hz ± 10 Hz
  • Power Factor > 0.99 (full load)
  • Current Harmonic Distortion < 3%


  • Power Factor 0.9
  • Voltage 220/230/240 Vac
  • Frequency 50/60 Hz ± 0.05 Hz
  • Voltage Harmonic Distortion < 3% (linear load)
  • Overload Capability < 105%: continuous, 105~125%: 1 minute, 125~150%: 30 seconds
  • Crest Factor 3:1


  • N-1K IEC C13 x 4
  • N-2K/3K IEC C13 x 6, C19 x 1


AC-AC:

  • N-1K 91%
  • N-2K/3K Up to 93%

 

Battery Voltage:

  • N-1K 24 Vdc
  • N-2K 48 Vdc
  • N-3K 72 Vdc

 

Typical Backup Time

  • 4.5 min.(full load), 13 min.(half load)

Recharge Time

  • 3 hrs to 90%

Charge Current

  • 1.5 A

 



Display

  • LCD panel

Interface

  • MINI Slot x 1, USB Port x 1

Conformance

  • Safety & EMC CE/RCM/EN62040-1/EN62040-2 Category C2

 

Environment

  • Operating Temperature 0~40ºC
  • Relative Humidity 5~95% (non-condensing)