Delta DPH 25 – 75/150/200 kW

Due to its 25% higher output of power compared to UPS systems with a power factor of 0.8, the Modulon DPH Series UPS is a modular UPS that is frequently utilized for essential operations. The highest level of availability is provided by the Modulon DPH Series, which was created to meet the most demanding datacenter needs. The real on-line, double conversion, three-phase Modulon DPH Series UPS system provides a scalable architecture for the best power solutions thanks to its modular design. It offers parallel 800kW capacity in addition to 25kW to 200kW of uninterruptible power.

The scalable architecture of the Modulon DPH Series is offered in a 19" enclosure and offers both vertical and horizontal extension for flexible installation configurations. Your power distribution integration can take place in parallel rack enclosures or in the same rack. The needs of the datacenter, not the constraints of the UPS system, ultimately determine the best placement.

For mission-critical applications, built-in redundancy ensures a constant power supply, and the Modulon DPH Series' fully fault-tolerant design provides self-redundancy for the control mechanism, cooling system, and power modules. Because all vital components are hot-swappable, the mean time to repair (MTTR) is almost zero. Full control logic enables the system to self-synchronize and switch to the backup in the event that the primary module fails, allowing for a smooth transition with no interruption to operations.

Model

Power Rating

Frame

Input

Output

Interface

Conformance

Other Features

Efficiency

Environemnt

DPH-75K

DPH-75K 25, 50, 75 kVA/kW


 

DPH-75K 75 kW



  • Nominal Voltage 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire +G)
  • Voltage Range 305~478 Vac (full load), 242~478 Vac (60% load)
  • Current Harmonic Distortion < 3%*
  • Power Factor > 0.99
  • Frequency 50/60 Hz


  • Voltage 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire +G)
  • Output Power Factor 1 (kVA=kW)
  • Voltage Harmonic Distortion ≤ 2% (linear load)
  • Voltage Regulation ±1% (static)
  • Frequency 50 or 60 Hz
  • Frequency Regulation ± 0.05 Hz
  • Overload Capacity ≤ 125%: 10 minutes, ≤ 150%: 1 minute


  • System communication port x 1, LCM port x 1, Parallel port x 2, Smart slot x 2, Output dry contact x 6, Input dry contact x 2, Battery dry contact x 2, REPO
  • Optional SNMP IPv6 card, ModBus card, Relay I/O card, Battery cabinet temperature sensor cable, Battery cabinet status detection kit


  • Safety & EMC
  • BSMI, CE


  • Parallel Redundancy and Expansion 
  • Module and system redundancy
  • Maximum 4 units
  • Emergency Power Off Local and remote
  • Battery Start Yes
  • Event Log 3000 records


  • AC-AC 96% (Tested by TÜV)
  • ECO Mode 99%


  • Operating Temperature 0~40˚C
  • Relative Humidity 0~95% (non-condensing)
  • Audible Noise (at one meter) < 62 dBA


DPH-150K 

DPH-150K 25, 50, 75, 100, 125, 150 kVA/kW

DPH-150K 150 kW


DPH-200K



DPH-200K 25, 50, 75, 100, 125, 150, 175, 200 kVA/kW

DPH-200K 200 kW